Service and maintenance
5.3 Maintenance following tripping of a molded case circuit breaker
3VA molded case circuit breakers with UL and IEC certification
Manual, 01/2019, L1V30435333-01
383
5.3
Maintenance following tripping of a molded case circuit breaker
If a 3VA UL molded case circuit breaker trips because of an overcurrent (overload, short
circuit) or fault current (ground fault), the cause of the trip must be identified and eliminated
before the molded case circuit breaker may be switched on again.
In the case of 3VA6 molded case circuit breakers, the cause of the trip can be output via the
EFB300 external function box. With electronic trip units ETU 5-series and 8-series, the cause
of tripping can be indicated on the LCD display and optionally transferred via communication
modules.
An inspection as described in chapter Regular maintenance (Page 382) should be carried
out after each trip by the trip unit. In addition, any black residue on the molded case circuit
breaker must be removed as it may contain conductive particles. The molded case circuit
breaker should then be switched on and off without load at least five times.