3.1 Use of the 3VA UL molded case circuit breakers in line protection
3VA molded case circuit breakers with UL and IEC certification
Manual, 01/2019, L1V30435333-01
111
Ground fault pickup setting values - I
g
Neutral current setting values - I
N
Overload protection L:
•
I
r
Adjustable in 10 steps from 0.4 to 1.0 x I
n
:
0.4 / 0.5 / 0.6 / 0.7 / 0.75 / 0.8 / 0.85 / 0.9 / 0.95 / 1.0
•
t
ld
Adjustable in 10 steps from 0.5 to 12 /15 s or 17 s:
t
ld
is the tripping time with 6 x I
r
The ETU330 LIG has a permanently active thermal memory.