Table 7-12
Overvoltage category
General
Overvoltage category II
In the application range of EN 60255-27
Overvoltage category III
7.3
Cable lengths
Table 7-13
Permitted cable lengths (copper cable - Fast Ethernet)
Cable type
Accessory (plug, outlet, TP cord) Permitted cable length
IE TP torsion cable
with IE FC Outlet RJ-45
+ 10 m TP cord
0 to 45 m
+ 10 m TP cord
with IE FC RJ-45 Plug 180
0 to 55 m
IE FC TP Marine Cable
IE FC TP Trailing Cable
IE FC TP Flexible Cable
with IE FC Outlet RJ-45
+ 10 m TP cord
0 to 75 m
+ 10 m TP cord
with IE FC RJ-45 Plug 180
0 to 85 m
IE FC TP standard cable
with IE FC Outlet RJ-45
+ 10 m TP cord
0 to 90 m
+ 10 m TP cord
with IE FC RJ-45 Plug 180
0 to 100 m
Table 7-14
Permitted cable lengths (copper cable - gigabit Ethernet)
Cable type
Accessory (plug, outlet, TP cord) Permitted cable length
IE FC Standard Cable, 4 × 2, 24
AWG
IE FC Flexible Cable, 4 × 2, 24
AWG
with IE FC RJ-45 Plug 180,
4 × 2
0 to 90 m
IE FC Standard Cable, 4 × 2, 22
AWG
with IE FC Outlet RJ-45
+ 10 m TP cord
0 to 60 m
+ 10 m TP cord
IE FC Flexible Cable, 4 × 2, 22
AWG
with IE FC Outlet RJ-45
+ 10 m TP cord
0 to 90 m
+ 10 m TP cord
Table 7-15
Permitted cable lengths (fiber-optic cable - Fast Ethernet)
Fiber-optic cable type
Permitted cable length
Attenuation
62.5/125 μm
50/125 μm,
0 to 5 km
≤1 dB/km at 1310 nm; 1200 MHz×km; maximum insertion loss
0.5 dB; 9 dB max. permitted FO cable attenuation at 3 dB link power
margin
Technical data
7.3 Cable lengths
SCALANCE X-300EEC
62
Compact Operating Instructions, 11/2019, A5E02630809-14
Содержание SCALANCE X-300EEC
Страница 10: ...Introduction SCALANCE X 300EEC 10 Compact Operating Instructions 11 2019 A5E02630809 14 ...
Страница 12: ...Safety notes SCALANCE X 300EEC 12 Compact Operating Instructions 11 2019 A5E02630809 14 ...
Страница 72: ...Dimension drawings SCALANCE X 300EEC 72 Compact Operating Instructions 11 2019 A5E02630809 14 ...
Страница 84: ...Index SCALANCE X 300EEC 84 Compact Operating Instructions 11 2019 A5E02630809 14 ...