The signaling contact can be subjected to a maximum load of 100 mA (safety extra‑low voltage
SELV, 24 V DC).
Table 6-1
Pin assignment of the 24 V DC signaling contact
Pin number
Assignment
Pin 1
F1
Pin 2
F2
To wire up the signaling contact, use a copper cable of category 18-12 AWG or cable with a
cross-section of 0.75 to 2.5 mm².
NOTICE
Laying the connecting cables of the signaling contact with the X‑300EEC
To improve the EMC properties (surge protection), the two connecting cables of the signaling
contact should be laid together.
6.6.2
Signaling contact 100 to 240 VAC / 60 to 250 VDC
WARNING
Danger from line voltage
Devices with this mark have a 100 to 240 VAC power supply.
This product can only function correctly and safely if it is transported, stored, set up, and
installed correctly, and operated and maintained as recommended.
Connecting and disconnecting may only be performed by an electrical specialist.
Connect or disconnect power supply cables only when the power is turned off.
Connecting
6.6 Signaling contact
SCALANCE X-300EEC
46
Compact Operating Instructions, 11/2019, A5E02630809-14