Power supply 100 AC .. 240 V / 24 .. 250 VDC
WARNING
Danger from line voltage
The SCALANCE X204RNA EEC has a power supply of 100 to 240 VAC or 24 to 250 VDC.
This product can only function correctly and safely if it is transported, stored, set up, and
installed correctly, and operated and maintained as recommended.
Connecting and disconnecting may only be performed by an electrical specialist. Connect or
disconnect power supply cables only when the power is turned off.
WARNING
The SCALANCE X204RNA EEC does not have an ATEX approval.
Devices with a 100 to 240 VAC or 24 to 250 VDC power supply are not approved for use in
hazardous areas according to EC‑RL‑-94/9 (ATEX).
NOTICE
Securing cables with dangerous voltage
Make sure that the connector cannot be released accidentally by pulling on the connecting
cable. Lay the cables in cable ducts or cable channels and secure the cables, where
necessary, with cable ties.
Protective ground
WARNING
PE connector of SCALANCE X204RNA EEC
Simple grounding via the housing is inadequate. For reliable operation, the PE cable must
be connected via the ground bolt. On the SCALANCE X204RNA EEC, the grounding bolt is
on the bottom of the device.
Connecting up
6.1 Power supply
SCALANCE X-200RNA
Operating Instructions, 10/2016, C79000-G8976-C342-04
65
Содержание SCALANCE X-200RNA
Страница 6: ...Table of contents SCALANCE X 200RNA 6 Operating Instructions 10 2016 C79000 G8976 C342 04 ...
Страница 12: ...Introduction SCALANCE X 200RNA 12 Operating Instructions 10 2016 C79000 G8976 C342 04 ...
Страница 16: ...Safety notices SCALANCE X 200RNA 16 Operating Instructions 10 2016 C79000 G8976 C342 04 ...
Страница 54: ...Descriptions of the products 4 8 LEDs SCALANCE X 200RNA 54 Operating Instructions 10 2016 C79000 G8976 C342 04 ...
Страница 62: ...Installation 5 3 Wall mounting SCALANCE X 200RNA 62 Operating Instructions 10 2016 C79000 G8976 C342 04 ...
Страница 70: ...Connecting up 6 4 Grounding SCALANCE X 200RNA 70 Operating Instructions 10 2016 C79000 G8976 C342 04 ...
Страница 142: ...Approvals and marking SCALANCE X 200RNA 142 Operating Instructions 10 2016 C79000 G8976 C342 04 ...
Страница 146: ...Technical specifications SCALANCE X 200RNA 146 Operating Instructions 10 2016 C79000 G8976 C342 04 ...