84/93
Building Technologies Division
User Manual RWF55...
CC1U7867en
Infrastructure & Cities Sector
14 Technical data
05.11.2013
14.3 Controller
outputs
OutP
Controller o
Galvanic separation between supply voltage, analog inputs, and controller outputs.
Reference!
See chapter 4.2
Galvanic separation
Relay K1
(NO contact)
1P, 1N
(burner release)
Contact rating
Max. 2 A at AC 240 V at cos
φ
>0.6
Contact life
250,000 switching cycles at high-fire
Contact protection
Varistor
Power supply for transducer G+, G-
DC 24 V
10%/max. 30 mA, short-circuit-
proof
The following relay data are those specified by the supplier.
Relay K2, KQ
(controlling element OPEN)
Contact rating
Max. 2 A at AC 450 V and cos
φ
>0.6
Contact life
200.000 switching cycles at high-fire
Contact protection
RC combination
Relay K3, KQ
(controlling element CLOSE)
Contact rating
Max. 2 A at AC 240 V at cos
φ
>0.6
Contact life
200.000 switching cycles at high-fire
Contact protection
RC unit
Relay K6
(NO contact)
, 6P, 6N
(multifunctional relay)
Contact rating
Max. 2 A at AC 240 V at cos
φ
>0.6
Contact life
200.000 switching cycles at high-fire
Contact protection
Varistor
Relay data are those specified by the supplier.
Analog output A+, A-
Voltage
DC 0...10 V short-circuit-proof
Load resistance
R
Last
≥
500
Accuracy
0.25%,
50 ppm/K
Current
0...20 mA/4...20 mA
Load resistance
R
Last
500
Accuracy
0.25%,
50 ppm/K
Baudrate 4800
Baud
9600 Baud
19200 Baud
38400 Baud
Protocol Modbus
Unit address
1...99
Only present with RWF55.6!
Interface RS-485
Profibus interface