71/93
Building Technologies Division
User Manual RWF55...
CC1U7867en
Infrastructure & Cities Sector
11 Modbus interface
05.11.2013
11.5 Device data
Address
Access
Data type
Signal reference
Parameter
0x8000 R/O Char12 ---
Software
version
0x8006 R/O Char14 ---
VdN
number
11.6 Device state
Address
Access
Data type
Signal reference
Parameter
0x0200 R/O Word ---
Outputs and states
Bit
0
Output
1
Bit
1
Output
3
Bit
2
Output
2
Bit
3
Output
4
Bit
8
Hysteresis
limitation
Bit
9
Control
system
Bit
10
Self-optimization
Bit
11
Second
setpoint
Bit
12
Measuring
range
overshoot
InP1
Bit
13
Measuring
range
overshoot
InP2
Bit
14
Measuring
range
overshoot
InP3
Bit
15
Calibration
mode
0x0201 R/O Word ---
Binary
signals and hardware detection
Bit
0
Operation
mode
2-stage
Bit
1
Manual
mode
Bit
2
Binary
input
D1
Bit
3
Binary
input
D2
Bit
4
Thermostat
function
Bit
5
First
controller
output
Bit 6
Second controller output
Bit
7
Alarm
relay
Bit
13
Analog
output
available
Bit
14
Interface
available