83/93
Building Technologies Division
User Manual RWF55...
CC1U7867en
Infrastructure & Cities Sector
14 Technical data
05.11.2013
14.2 Monitoring the measuring circuit
In the event of error, the outputs assume defined states (configurable).
Measuring
transducer
Measured value
crossed limit
Sensor/line has
short-circuit
Sensor/line
interrupted
Resistance
thermometer
●
●
●
Thermal elements
●
---
●
Voltage
DC 1...5 V
●
●
●
DC 0...5 V
(
●
) --- ---
DC 0...10 V
(
●
) --- ---
Current
DC 4...20 mA
●
●
●
DC 0...20 mA
(
●
)
---
---
●
= detected
(
●
)
= detected only if measuring range is exceeded
---
= not detected
Reference!
See chapter 13.1
Alarm messages.