6 Operation
05.11.2013
6.3 User
level
This level is started from the basic display.
Setpoints
SP1
,
SP2
or
dSP
can be altered.
The values of the analog inputs
InP1
,
InP2
,
InP3
and
SPE
(external setpoint) and
InP3
(actual angular positioning between 0...100%) can be displayed.
Changing SP1, SP2 or dSP.
*
From the basic display, press
so that
OPr
appears
*
Press
so that
SP1
appears
*
Press
and
SP1
flashes
*
Press
or
to adjust the required setpoint and press
to confirm
SP2
only appears if
setpoint changeover
is set (binary input
bin1
= 1).
*
From the basic display, press
so that
OPr
appears
*
Press
so that
SP1
appears
*
Press
to change over to
SP2
*
Press
and
SP2
flashes
*
Press
or
to adjust the required setpoint and press
to confirm
dSP
only appears if
setpoint shifting
is set (binary input
bin1
= 2).
*
From the basic display, press
so that
OPr
appears
*
Press
so that
SP1
appears
*
Press
to change over to
dSP
*
Press
and
dSP
flashes
*
Press
or
to adjust the required setpoint and press
to confirm
Timeout after about 180 seconds.
Note!
If the setpoint is not stored, the basic display changes after the timeout
tout
and the
former setpoint is maintained.
The value changes only within the permitted range.
Changing the
setpoints
SP1
SP2
dSP
Timeout