
79/93
Building Technologies Division
User Manual RWF55...
CC1U7867en
Infrastructure & Cities Sector
14 Technical data
05.11.2013
14 Technical
data
14.1 Inputs
14.1.1 Analog
input
InP1
(actual value)
For resistance thermometers, thermal elements or standard signals with 2nd order
digital filters (configurable).
Sampling time
250 ms
Type Measuring
range
Measuring
accuracy
a
Impact of
ambient
temperature
Pt100; DIN EN 60751
-200...850 °C
(-328...1562 °F)
0,05%
50 ppm/K
Pt1000; DIN EN 60751
-200...850 °C
(-328...1562 °F)
0,05%
50 ppm/K
LG-Ni1000
-50...+160 °C
(-58...320 °F)
0,05%
50 ppm/K
0...135
0,05%
50 ppm/K
a
Accuracies relate to the maximum measuring range.
Line resistance
Max. 30
per line with 3-wire circuit
Line balancing
Not required with 3-wire circuits.
With 2-wire circuits, line balancing can be
performed by making an actual value
correction
Type
Measuring
range
Measuring
accuracy
a
Impact of ambient
temperature
Fe-CuNi
J
DIN EN 60584
-200...+1200 °C
(-328...+2192 °F)
0.25%
100 ppm/K
NiCr-Ni
K
DIN EN 60584
-200...+1372 °C
(-328...+2502 °F)
0.25%
100 ppm/K
Cu-CuNi
T
DIN EN 60584
-200...+400 °C
(-328...+752 °F)
0.25%
100 ppm/K
NiCrSi-NiSi
N
DIN EN 60584
-100...+1300 °C
(-148...+2372 °F)
0.25%
100 ppm/K
Pt-RhPt
S
DIN EN 60584
-50...+1768 °C
(-58...+3214 °F)
0.25%
100 ppm/K
Pt-RhPt
R
DIN EN 60584
-50...+1768 °C
(-58...+3214 °F)
0.25%
100 ppm/K
Pt-RhPt
B
DIN EN 60584
0...1820 °C
(32...3308 °F)
0.25%
100 ppm/K
a
Accuracies relate to the maximum measuring range.
Cold-function temperature
Internal
Resistance
thermometers
Thermal elements