Infrastructure & Cities Sector
5 Operating modes
05.11.2013
5.2.4 2-stage burner, analog output
In this case, a digital standard signal switches the second stage on via the analog
output (terminals
A+
and
A-
) when reaching switch-on threshold
HYS1
and off at the
lower switch-off threshold
HYS2
.
A
7866d08/0911
Figure 11: Control sequence of 2-stage burner, analog output
If the controller is set to cooling mode, the respective values of
HYS4
,
HYS5
and
HYS6
apply.
Starting from a high actual value, the controller now controls the connected cooling
equipment in low-fire operation. In high-fire operation, the second stage and thus the
cooling output are controlled via relays K2 and K3 or the analog output. The response
threshold (q) calculates automatically (now in the reverse sense) the point from which
the cooling output is to be increased.
Cooling controller