25 Function block "Service functions and general settings"
23.10.2002
T
AM
Flow temperature setpoint
Operating line 165
1 + s
Parallel displacement of,
heating curve, operating line 72
1 + s
25
24B0
5
e
T
V
T
AM
T
VS
Heating curve
T
Vw
T
VS
s
Setting knob
on controller
s
Slope
T
AM
Composite outside temperature
T
VS
Flow temperature setpoint (generated via the heating curve)
TVw
Flow temperature setpoint
25.2.2 Heating
curve
The display shows the resulting heating curve which is composed of the following vari-
ables:
•
Basic setting with the little bar or on operating lines 14 and 15
•
Position of the knob for room temperature readjustments
•
Parallel displacement (setting on operating line 72)
The display also shows the 2 flow temperature setpoints:
•
TV1; current setpoint at an outside temperature of +15 °C
•
TV2; current setpoint at an outside temperature of
−
5 °C
With demand-compensated control (plant types 4–x, 5–x, and 6–x), the display shows -
-- ---.
TV1, TV2
Operating line 166
Parallel displacement of
heating curve, operating line 72
1 + s
25
2
4
B06
e
T
V
T
AM
Heating curve
TV2
S
TV1
S
+15 °C
-5 °C
TV1
S
+ TV2
S
TV1
,
TV2
1 + s
Setting knob
on controller
s
Slope
TV1
Actual flow temperature setpoint at +15 °C
TV2
Actual flow temperature setpoint at
−
5 °C
TV.
S
Flow temperature setpoint (generated via the heating curve)
25.2.3
Hours run counter
The number of controller operating hours is displayed. Whenever operating voltage is
present, the RVL471 counts the hours.
The maximum reading is limited to 500,000 hours (57 years).
25.2.4 Software
version
The controller displays the software version in use.
Generation of the flow
temperature setpoint
Display of heating
curve data