Siemens Building Technologies
Basic Documentation RVL471
CE1P2524E
HVAC Products
3 Fundamentals
23.10.2002
3.6 Manual
operation
The RVL471 can be switched to manual operation. In this case, the control will be
switched off. In manual operation, the various actuating devices behave as follows
:
•
Heating circuit mixing valve: This mixing valve is not under voltage, but can be manu-
ally driven to any position by pressing the manual buttons
( = closing,
= opening). The heating circuit pump / circulating pump is continuously running.
•
Boiler: The 2 burner stages are continuously on. The manual button
can be used to
switch the second stage on and off. Pump M1 is continuously running
•
D.h.w. charging pump: The charging pump is continuously running
•
D.h.w. changeover valve: The diverting valve is always in the ”Heating circuit” position
•
D.h.w. slipper / seat valve: This valve is driven to the fully closed position, in which
case the closing time is five times the set running time. Then, it is deactivated
•
Circulating pump M4: Continuously running
•
Electric immersion heater K6: Continuously released
•
Multifunctional relay: Continuously energized
Manual operation also negates any overriding of the controller's operating mode
(bridging of H1–M).
3.7
Plant type and operating mode
Depending on the selected type of plant, the following operating modes are available:
Plant type
1–0
YES
YES
YES
YES
NO
YES
1–1, 1–2, 1–4, 1–5
YES
YES
YES
YES
YES
YES
2–0
YES
YES
YES
YES
NO
YES
2–1, 2–2, 2–3, 2–5
YES
YES
YES
YES
YES
YES
3–0
YES
YES
YES
YES
NO
YES
3–1, 3–2, 3–3, 3–4, 3–5
YES
YES
YES
YES
YES
YES
4–0
YES
NO
NO
NO
NO
YES
4–1, 4–2, 4–5
YES
NO
NO
NO
YES
YES
5–0
YES
NO
NO
*)
NO
YES
5–1, 5–2, 5–4, 5–5
YES
NO
NO
*)
YES
YES
6–0
YES
NO
NO
NO
NO
YES
6–1, 6–2, 6–5
YES
NO
NO
NO
YES
YES
*) Depending on the boiler's operating mode:
Boiler with automatic shutdown: NO
Boiler with manual shutdown: YES