87/118
Siemens Building Technologies
Basic Documentation RVL471
CE1P2524E
HVAC Products
25 Function block "Service functions and general settings"
23.10.2002
25.3.2 Relay
test
The eight output relays can be individually energized. Depending on the type of plant,
the following codings apply:
Input
Plants with a valve (plant types
1–x, 3–x, 4–x, and 6–x)
Plants with a burner (plant types
2–x, and 5–x)
0
Normal operation
Normal operation
1
All contacts open
All contacts open
2
Heating circuit valve OPEN (Y1)
Burner stage 1 ON (K4)
3
Heating circuit valve CLOSED (Y2)
Burner stages 1 and 2 ON
4
Heating circuit pump / circulating
pump ON (M1)
Heating circuit pump / circulating
pump ON (M1)
5
Charging pump / diverting valve ON
(M3/Y3)
Charging pump / diverting valve ON
(M3/Y3)
6
Circulating pump ON (M4)
Circulating pump ON (M4)
7
Multifunctional relay energized (K6)
Multifunctional relay energized (K6)
8
D.h.w. valve OPEN (Y7)
D.h.w. valve OPEN (Y7)
9
D.h.w. valve CLOSED (Y8)
D.h.w. valve CLOSED (Y8)
There are 4 choices to terminate the relay test:
•
Entry of 0 on the operating line
•
Leaving the setting level by pressing button
or
•
Leaving the setting level by pressing the Info button or any of the operating mode but-
tons
•
Automatically after 30 minutes
25.3.3 Sensor
test
The connected sensors can be checked on operating line 163. In addition, if available,
the current setpoints and limit values are displayed.
On the display, the current setpoints are identified by SET, the actual values by
ACTUAL (also refer to section “28 Handling”)
The 9 temperatures can be called up by entering 0...8:
Input
Display SET
Display ACTUAL
0
No display
Actual value of outside sensor at
terminal B9.
If the outside temperature is deliv-
ered via the data bus, the display
shows ---
1
Setpoint of flow / boiler temperature.
With the plant types using a boiler, the
switch-off point is displayed. If there is
no demand for heat, the display shows
---
Actual value of flow / boiler tem-
perature sensor at terminal B1
2
Setpoint of room temperature.
With the plant types with no heating
circuit, the display shows ---
Actual value of room temperature
sensor at terminal B5
3
Setpoint of room temperature.
With the plant types with no rooms,
the display shows ---
Actual value of room unit sensor at
terminal A6