47/118
Siemens Building Technologies
Basic Documentation RVL471
CE1P2524E
HVAC Products
10 Function block "Space heating"
23.10.2002
10.7 Generation of setpoint
10.7.1 Weather-compensated
control
Weather-compensated control is used with plant types 1
−
x, 2
−
x and 3
−
x. The setpoint is
generated via the heating curve as a function of the outside temperature. The tem-
perature used is the composite outside temperature.
Composite outside
temperature
Knob on
room unit *
Heating curve
Knob on
controller
Flow temperature
setpoint T
Vw
Setpoint on
operating line 165
Parallel displacement of
heating curve, operating line 72
LPB
SYNERGYR
OZW30
Room setpoint
or
s
1 + s
20 °C
Operating line
1, 2 or 3
1 + s
25
24B
01
e
LPB
Data bus
OZW30 SYNERGYR central unit
s
Slope
*
Active only with room unit level
The impact of the central unit OZW30 is described in section “27.1.4 Combination with
SYNERGYR central unit OZW30 described.
10.7.2 Demand-compensated
control
Demand-compensated control is used with plant types 4
−
x, 5
−
x, and 6
−
x.
The setpoint is delivered to the RVL471 via the data bus (LPB) in the form of a heat
demand signal. In that case, the outside temperature will not be taken into considera-
tion.