29 Combination with PPS devices
27.05.2004
29
Combination with PPS devices
29.1 General
•
PPS units are digital peripheral devices for connection to the PPS (point-to-point
interface, terminals A6–MD) of the controller. Such units are presently the following:
−
Room units QAW50, QAW50.03 and QAW70
−
Room temperature sensor QAA10
•
The room temperature acquired with a room unit is adopted by the controller. If the
room temperature shall not be included in the control functions, the room influence
on operating line 70 must be set to 0. The other room unit functions will then be
maintained
•
If an inadmissible unit is connected, the RVD240 identifies a fault. A room unit will be
switched to the passive state; this means that all entries made on the room unit will
have no effect
•
The operating mode of d.h.w. heating is independent of the operating mode of a
room unit. One exception is the holiday function (refer to subsection 29.3.6 "Entry of
holiday periods ")
•
The room unit acts fully on the controller also when, on the controller, an operation
locking function is activated (operating lines 195 and / or 196: Setting
>
0).
•
A short-circuit at the PPS leads to an error message; an open-circuit represents a
permitted status (no device present)
29.2 Combination with room unit QAW50...
29.2.1 General
Room unit QAW50..., with room sensor, knob for
room temperature setpoint readjustments and
economy button
The QAW50... can act on the RVD240 as follows:
•
Overriding the operating mode
•
Readjustment of room temperature
For this purpose, the QAW50... has 3 operating elements:
•
Operating mode button
•
Economy button (also called presence button)
•
Knob for readjusting the nominal room temperature setpoint
29.2.2 Overriding the operating mode
From the QAW50..., the operating mode of the RVD240 can be overridden. This is
made with the operating mode button and the economy button.
To enable the room unit to act on the RVD240, the controller must be in automatic mode.
The actions of the QAW's operating mode button on the RVD240 are as follows: