87/126
Siemens Building Technologies
Basic documentation RVD240
CE1P2384en
HVAC Products
25 Function block Test and display
27.05.2004
25
Function block Test and display
25.1 Operating
lines
Line
Function, parameter
Unit
Factory setting
Range
161
Sensor test
0
0...11
162
Display of setpoint
0
0...11
163
Relay test
0
0...10
164
Speed of speed-controlled pump
Display function
165
Display of digital inputs
Display function
169
Display of active limitations
Display function
170
Software version
Display function
25.2 Sensor
test
The sensor test includes the temperature acquired with each sensor and the voltage
present at the analog input. Interrogation is made with the setting buttons
and
.
To identify the acquired variable, a code is used.
The numbers on the display have the following meaning:
--.-
= open-circuit / no sensor connected to input B9
oo.o = short-circuit at input B9
---
= open-circuit / no sensor present
ooo = short-circuit at the other inputs
Code
Input
Acquired variable, measured value
0
B9
Weather (outside temperature)
1
B1
Flow temperature heating circuit 1 or heat converter
2
B3
D.h.w. flow temperature
3
A6
Room unit heating circuit 1
4
A6
Room unit heating circuit 2
5
B7
Return temperature
6
B71
Return temperature
7
B72
Return temperature
8
B31
Storage tank temperature
9
B32
Storage tank temperature
10
B12
Flow temperature heating circuit 2
11
U1
DC 0...10 V / 0…130 °C
25.3 Setpoint test
The setpoint test includes the display of the setpoint assigned to each sensor. Interro-
gation is made with the setting buttons
and
. To identify the acquired variable, a
code is used.
--- means: No setpoint available
Code
Input
Setpoint of the …
0 B9
composite
outside
temperature
1
B1
flow temperature heating circuit 1 or heat converter
2
B3
d.h.w. flow temperature
3
A6
room unit heating circuit 1
4
A6
room unit heating circuit 2
5
B7
return temperature
6
B71
return temperature
7
B72
return temperature
8
B31
storage tank temperature