64/126
Siemens Building Technologies
Basic documentation RVD240
CE1P2384en
HVAC Products
16 D.h.w. heating
27.05.2004
This function can be activated or deactivated on operating line 191 (function block
"Miscellaneous"):
0 = function deactivated
1 = function activated
16.1.5 Protection
against
discharging
With the types of plant having a storage tank connected on the secondary side (coil
type or stratification storage tank, plant types 2–x and 3–1), protection against d.h.w.
discharging is provided
during
pump overrun.
If the common flow temperature or the flow temperature in the intermediate circuit is
lower than the d.h.w. temperature (in the case of two storage tank sensors, the lower
actual value applies), overrun of the d.h.w. pump in the intermediate circuit will be
stopped prematurely. This prevents the d.h.w. from cooling down unnecessarily.
On operating line 110, protection against discharging during overrun of the d.h.w. pump
can be activated (0 = no protection, 1 = protection against discharging active).
With the plant types using a coil type storage tank, it is recommended to have protection
against discharging always activated. This applies to plant types 1–9, 2–1, 2–2, 3–1 and
4–9.
Plant type 2–6 with a storage tank charging pump features d.h.w. discharging protec-
tion
during charging
. This deactivates the storage tank charging pump when flow
temperature B1 falls by 2 K below the storage tank temperature. In the case of two
storage tank sensors, the higher actual value applies.
With plant types x–8 and x–9 with a storage tank connected on the primary side, pro-
tection against discharging is not required during charging.
16.1.6 Protection
against
overtemperatures
If the flow temperature is too high, the heating circuit pump will overrun before d.h.w.
heating is started.
16.1.7 Storage tank with electric immersion heater
If an electric immersion heater is used in a storage tank, the setpoint adjustment is no
longer valid since in that case, the thermostat of the electric immersion heater will en-
sure temperature control of the storage tank. When, in the summer, an electric immer-
sion heater is used for d.h.w. heating, the d.h.w. setpoint must therefore be lowered to
the setpoint for frost protection. This is achieved by switching off the d.h.w. heating
mode.
16.2 D.h.w. heating with stratification storage tank
This section only describes the functions used in addition to d.h.w. heating with storage
tanks.
16.2.1 General
D.h.w. heating with stratification storage tanks is covered by plant types 1–8, 2–6, and
4–8. With these types of plant, separate heat exchangers are used for space heating
and d.h.w. heating. They can be connected either parallel to or in series with the heat-
ing circuit.
The d.h.w. flow temperature can be controlled with the help of one or two flow sensors;
variable speed control of the storage tank charging pump is also possible.
These types of plant require no flow switch.