RUGGEDCOM RSG2100PF
Installation Guide
Chapter 6
Certification
EMC and Environmental Type Tests
41
Test
Description
Test Levels
Severity Levels
Signal Ports
IEC 61000-4-16
Mains Frequency Voltage
AC and DC Power Ports
30 V Continuous
300 V for 1s
4
IEC 61000-4-17
Ripple on DC
Power Supply
DC Power Ports
10%
3
IEC 61000-4-18
Damped Oscillatory Wave
Slow Damped
2.5 kV Common Mode
on Power and Signal
1.0 kV Differential
Mode on Power
3
IEC 61000-4-29
Voltage Dips
and Interrupts
DC Power Ports
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
Signal Ports
2 kV (Fail-Safe
Relay Output)
DC Power Ports
2 kV
Dielectric Strength
AC Power Ports
2 kV
Signal Ports
5 kV (Fail-Safe
Relay Output)
DC Power Ports
IEC 60255-5
HV Impulse
AC Power Ports
5 kV
EMC Immunity Type Tests per IEEE 1613
NOTE
The RUGGEDCOM RSG2100PF meets Class 2 requirements for an all-fiber configuration and Class 1
requirements for copper ports. Class 1 allows for temporary communication loss, while Class 2 requires
error-free and interrupted communications.
Description
Test Levels
Enclosure Contact
±2 kV
±4 kV
±8 kV
ESD
Enclosure Air
±4 kV
±8 kV
±15 kV
Radiated RFI
Enclosure Ports
35 V/m
Signal Ports
4 kV @ 2.5 kHz
DC Power Ports
4 kV
AC Power Ports
4 kV
Fast Transient
Earth Ground Ports
4 kV
Signal Ports
2.5 kV Common Mode @ 1 MHz
Oscillatory
DC Power Ports
2.5 kV Common