Chapter 6
Certification
RUGGEDCOM RSG2100PF
Installation Guide
42
EMC and Environmental Type Tests
Description
Test Levels
1 kV differential mode @ 1 MHz
AC Power Ports
2.5 kV Common
1 kV differential mode @ 1 MHz
Signal Ports
5 kV (Fail-Safe Relay Output)
DC Power Ports
5 kV
HV Impulse
AC Power Ports
5 kV
Signal Ports
2 kV
DC Power Ports
2 kV
Dielectric Strength
AC Power Ports
2 kV
Damped Oscillatory
Magnetic Field
Enclosure Ports
100 A/m
Environmental Type Tests
Test
Description
Test Levels
Severity Level
IEC 60068-2-1
Cold Temperature
Test Ad
-40 °C (-40 °F), 16 Hours
IEC 60068-2-2
Dry Heat
Test Bd
85 °C (185 °F), 16 Hours
IEC 60068-2-30
Humidity (Damp Heat, Cyclic)
Test Db
95% (non-condensing),
55 °C (131 °F), 6 cycles
IEC 60068-21-1
Vibration
2g @ 10-150 Hz
IEC 60068-21-2
Shock
30 g @ 11 ms
IEC 60068-2-78
Humidity (Damp Heat, Steady State)
Test Cab
10 days @ 55 °C (131 °F)
and 93% Relative Humidity
IEC 60068-2-14
Change of Temperature
Test Nb
5 Cycles, -40 to 85° C (40 to 185° F)
IEC 60255-21-2
Bump
10 g @ 16 ms
Class 1
IEC 60255-21-3
Seismic
Method A, Class 2
Class 1