Siemens Building Technologies
Data sheet RMH760
CE1N3131en
HVAC Products
03.07.2003
Technical design
The controller is supplied with 28 basic types of heating plant preprogrammed. They
have been selected to cover the majority of standard applications. Some of them re-
quire extension modules.
When commissioning a plant, the relevant basic plant type must be entered. All associ-
ated functions, terminal assignments, settings and displays will automatically be acti-
vated, and parameters not required will be deactivated.
Precontrol can only be provided by the controller. There are 2 choices:
With mixing valve:
With system pump:
P1 P2
31
31
S
01
Y1
B1
M1
B7*
B7
31
31
S
02
B1*
M1
B1 Flow
temperature
sensor
B1* Flow temperature sensor
(optional, for display only)
B7 Return temperature sensor (op-
tional, for minimum limitation)
B7* Return temperature sensor (op-
tional, for maximum limitation)
M1 System pump (can be a twin
pump)
Y1 Mixing
valve
Measuring input B7 for the return temperature can be configured for either minimum or
maximum limitation.
The control of 1 or 2 heating circuits can be provided either by the controller or the
RMZ782 heating circuit module. The available choices are the same with both types of
unit, provided the required connection terminals for the desired auxiliary function are
present.
Please also note the following:
•
If the controller and heating circuit module do not have a sufficient number of config-
urable connection terminals, an additional extension module can be used
•
If the controller is used as a primary controller, the RMZ782 heating circuit module
must be used for the control of the heating circuit
•
A second heating circuit must be controlled with the RMZ782 heating circuit module
•
Measuring input B7 for the return temperature can be configured for either minimum
or maximum limitation
Y1
M1
B1
B7
B7*
B9
A5
B5
B91
B92
31
31
S
39
R5
A5 Room unit (optional)
B1 Flow
temperature
sensor
B5 Room temperature sensor (optional)
B7 Return temperature sensor (optional, for minimum limitation)
B7* Return temperature sensor (optional, for maximum limitation)
B9 Outside
sensor
B91 Solar impact sensor (optional)
B92 Wind effect sensor (optional)
M1 Heating circuit pump (can be a twin pump)
R5 Remote setpoint adjuster (optional)
Y1 Mixing
valve
Mode of operation
Use of individual de-
vices
Precontrol
Heating circuit control