14/16
Siemens Building Technologies
Data sheet RMH760
CE1N3131en
HVAC Products
03.07.2003
Terminal Function
Signal receiver
Type of contact
Y13
Input for Y14
Y14
Mixing valve opens
3-position actuator
N.O.
Y23
Input for Y24
Y24
Mixing valve closes
3-position actuator
N.O.
Q13
Input for Q14
Q14 Heating
circuit
pump on
Heating circuit pump M1
N.O.
Analog input signals
Measuring variable, function
Signal source
Range
Return temperature
1 or 2 sensors LG-Ni 1000
–50…+150 °C
Wind speed
Wind effect sensor 0…20 m/s
DC 0…10 V
Intensity of solar radiation
Solar impact sensor 0…1000 W/m
2
DC
0…10
V
Room temperature
1 or 2 sensors LG-Ni 1000
–50…+50 °C
Room temperature setpoint
Room unit QAA25
5…35 °C
Room temperature setpoint
Remote setpoint adjuster BSG21.1
0…50 °C
Room setpoint readjustment
Room temperature sensor QAA27
±3 K
Room setpoint readjustment
Remote setpoint adjuster BSG21.5
±3 K
Heat demand
Consumer
DC 0…10 V
Digital input signals
Function, variable
Signal source
Range
Room operating mode
External contact
On / off
Timer function
External contact
On / off
Heat demand
External contact
On / off
Special day
External contact
On / off
Holidays
External contact
On / off
Error message 1
External contact
On / off
Error message 2
External contact
On / off
Error message 3
External contact
On / off
Error message 4
External contact
On / off
Type of signal
Signal receiver
Range
Positioning signal
Modulating actuator
0…100 %
Heat demand
Primary controller
Configurable
Changeover to connection Q71–Q74 …
Rated voltage range
in the event of an urgent error message
AC 24…230 V
in the event of an error message that is not urgent
AC 24…230 V
when reaching the heating limit of heating circuit 1
AC 24…230 V
when reaching the heating limit of heating circuit 2
AC 24…230 V
during occupancy time of heating circuit 1
AC 24…230 V
during occupancy time of heating circuit 2
AC 24…230 V
when the outside temperature falls
AC 24…230 V
when there is a heat demand
AC 24…230 V
For the actuating devices
Configurable connection
terminals
X3, X4 and X5 for input
signals
Y9 for continuous output
signal DC 0…10 V
Q71 / Q72 / Q74 for
changeover contacts