12/16
Siemens Building Technologies
Data sheet RMH760
CE1N3131en
HVAC Products
03.07.2003
Perm. resistance
Contacts
closed
Contacts
open
max. 200
Ω
min. 50 k
Ω
Output voltage
DC 0…10 V
Output current
±
1 mA
Max. load
continuous short-circuit
External supply line fusing
Non-renewable fuse (slow)
Automatic line cutout
Release characteristic
max. 10 A
max. 13 A
B, C, D to EN 60 898
Cable length
max. 300 m
Relay contacts
Switching
voltage
AC
current
– At 250 V
– At 19 V
Switch-on
current
max. AC 265 V / min. AC 19 V
max. 4 A res., 3 A ind. (cos
φ
= 0.6)
min. 5 mA
min. 20 mA
max. 10 A (1 s)
Contact life at AC 250 V
At 0.1 A res.
At 0.5 A res.
At 4 A res.
Red. factor at ind. (cos
φ
= 0.6)
guide values:
2×10
7
cycles
4×10
6
cycles (N. O.)
2×10
6
cycles (changeover)
3×10
5
cycles (N.O.)
1×10
5
cycles (changeover)
0.85
Insulating strength
−
Between relay contacts and system electronics (reinforced
insulation)
−
Between neighboring relay contacts (operational insulation),
Y1
⇔
Y2; Q1
⇔
Q7
−
Between relay groups (reinforced insulation),
(Y1, Y2)
⇔
(Q1, Q7)
AC 3750 V, to EN 60 730-1
AC 1250 V, to EN 60 730-1
AC 3750 V, to EN 60 730-1
Voltage
AC 24 V
Power supply external
devices (G1)
Current
max. 4 A
Konnex bus
Type of interface
Bus loading number
Bus power supply (decentral, can be switched off)
Power failure of short duration to EN 50 090-2-2
Konnex-TP1
2.5
25 mA
100 ms with 1 extension module
Extension bus
Connector
specification
Number of plugging cycles
4 contacts SELV/PELV
max. 10
Service tool connection facility RJ45-connector
For passive measuring and positioning signals
LG-Ni 1000
0…1000
Ω
1000…1235
Ω
Contact
sensing
max. 300 m
max. 300 m
max. 300 m
max. 300 m
(measuring errors can be corrected
on the "Settings > Inputs" menu)
For DC 0…10 V measuring and control signals
refer to Data Sheet of the signal
delivering device
For Konnex bus
Type
of
cable
max. 700 m
2-core without screening, twisted
pairs
Connection terminals
For
wires
For stranded wires without ferrules
For stranded wires with ferrules
spring cage terminals
0.6 mm dia. …2.5 mm
2
0.25…2.5 mm
2
0.25…1.5 mm
2
Connection facility for Konnex bus
wires cannot be interchanged
Positioning output Y9
Switching outputs
(Q…)
Interfaces
Perm. cable lengths
Electrical connections