25
MAN-100472
RD150 - Operating Instructions
57030-EN-180717
The following languages are available:
•
German
•
English
•
French
•
Spanish
•
Russian
•
Italian
•
Dutch
•
Portuguese
•
Turkish
•
Polish
•
Czech
In this menu item you define the indication of the measured values
on the display. The selection comprises the current value in mA or as
scaled value as well as the HART values PV, SV, TV, QV.
The display values can be adjusted separately.
The default setting for the display value is "
Current
".
The display and adjustment module has a backlight for the display.
In this menu item you can switch on the lighting. You can find the
required operating voltage in chapter "
Technical data
".
The lighting is switched off in delivery status.
Note:
The lighting switches off automatically when the current in the signal
circuit is lower than 4 mA.
It switches on automatically when the current in the signal circuit is
4 mA or higher.
To damp process-dependent measured value fluctuations, set an
integration time of 0 … 999 s in this menu item. The increment is 0.1 s.
The entered integration time influences the current value and the
display. The HART value remains unaffected.
Setup - Display, indica-
tion value 1 to 4
Setup - Display, lighting
Setup - Damping