19 / 42
Siemens
VAV compact controller G..B181.1E/3 | VAV modular controller ASV181.1E/3
CE1P3544en
Building Technologies
2016-02-26
4
Electrical and mechanical installation
4.1
Mechanical installation / mounting
For mounting and limitations on mounting (location / position), consulting the
mounting instruction M3544 ([2]) or M3545 ([4]) is mandatory.
The permissible ambient temperature and ambient humidity must be observed.
The actuator may only be manually operated when
separated from power
supply
.
If required, the angular rotation can be set by appropriate adjustment of the
adjusting screw.
When using the connecting cable with
the 6- or 7-pin plug
, attach the strain relief
strip at the cable to the VAV compact and modular controllers as shown in the
following illustration.
1
2
3
4
5
AST11
1 PC (with ACS931 or ACS941)
2 G..B181.1E/3
3 ASV181.1E/3
4 Connection to AST11
5 Strain relief strip
1
2
3
4
5
5
6
1 AST10
2 G..B181.1E/3
3 G..B181.1E/KN
4 ASV181.1E/3
5 Connection to AST10
6 Strain relief strip
Mounting and mounting
limitations
Environmental conditions
Manual control
Mechanical limitation of
angular rotation
Strain release strip
Connection to PC with
AST11
Connection to AST10