28 / 42
Siemens
VAV compact controller G..B181.1E/3 | VAV modular controller ASV181.1E/3
CE1P3544en
Building Technologies
2016-02-26
5.4 Setting
examples
5.4.1 Symbols and parameters
Volume symbols with “point” (
V
) and without point (V) shall have the same
meaning, i.e., they all shall refer to volume flows.
V
Volume flow [%]
min
V
Minimum volume flow [%]
max
V
Maximum volume flow [%]
supply_ air
V
Volume flow of supply air controller [%]
r
extract_ ai
V
Volume flow of extract air controller [%]
master
V
Volume flow of supply air controller (Master) [%]
slave
V
Volume flow of extract air controller (Slave) [%]
5.4.2
Min/max control by the supervisory controller
When setting the minimum / maximum air volume flow in the supervisory controller,
the VAV compact controller has to be configured with
min
V
= 0% and
max
V
= 100 %.
VAV ratio control 1 : 1
Supply air
Extract air
min
V
max
V
min
V
max
V
Supervisory controller
20 %
80 %
20 %
80 %
VAV compact controller
0 %
100 %
0 %
100 %
Reference signal: Y
supply_air
= Y
extract_air
= 35 %
Result:
V
supply_air
= V
extract_air
= 35 %
min
V
max
V
supply_ air
V
V
min
V
max
V
V
r
extract_ ai
V
Legend to the setting
examples
Setting example A1