33 / 42
Siemens
VAV compact controller G..B181.1E/3 | VAV modular controller ASV181.1E/3
CE1P3544en
Building Technologies
2016-02-26
VAV ratio control, 20 % constant excess supply air volume flow (positive
pressure in the room)
Supply air (Master)
Extract air (Slave)
min
V
max
V
min
V
max
V
Supervisory controller
0 %
100 %
0 %
100 %
VAV compact controller
20 %
80 %
-20 %
80 %
Reference signal: Y
master
= 25 %
Result:
V
master
= 35 %, V
slave
= 15 %
min
V
max
V
V
min
V
max
V
V
master
V
slave
V
VAV ratio control, 20 % constant excess extract air volume flow (negative
pressure in the room)
Supply air (Master)
Extract air (Slave)
min
V
max
V
min
V
max
V
Supervisory controller
0 %
100 %
0 %
100 %
VAV compact controller
20 %
80 %
20 %
120 %
Reference signal: Y
master
= 25 %
Result:
V
master
= 35 %, V
slave
= 55 %
min
V
max
V
V
min
V
max
V
V
master
V
slave
V
Setting example C2