3.3.2 Connection
diagrams
N1
G..B181.1E/3
or
ASV181.1E/3
N2
Room temperature controller, e.g.
RCU61.1
S1
Window switch (window closed = contact open)
Y1 OpenAir actuator, e.g.
GCA131.1E
(for non-spring return actuators,
connection G0 is not used)
a)
To actuator for "Heating"
b) To slave controller
c)
Crimping sleeve connection (4 x AMP butt joints are enclosed with the unit)
The operating voltage fed to terminals G and G0 must comply with the
requirements for SELV or PELV
Use safety isolating transformers with double insulation conforming to EN 61558;
they must be suited for 100 % on time
Control loop without communication, e.g. with
G..B181.1E/3
“con” mode and room
temperature controller
RCU61...
Operating mode “STP”
Legend to the connection
diagrams 1 through 4
Connection diagram 1
(G..B181.1E/3)