Figure 2
Rear View of the ACM-RK

TBM-2

TMM-1

MMM-1

P1

P3

P5

P7

P8

P6

P4

NEW CABLE FROM

CABLES-RK KIT

TO MMB-2

NEW CABLE FROM

CABLES-RK KIT

EXTENSION FROM

CABLES-RK KIT

EXISTING

MMM-1 CABLE

TO ANN-1

(MKB-RK)

ACM-1

ACM-RK

PIM-1

switch S1 to set the network address of the
MKB-3. Refer to Table 3 for switch settings.

2. The MKB-3 module address is always set

within network addresses 248 through 251.

3. One supervised MKB-3 must be installed

at network address 251. Other supervised
MKBs may be at the other addresses.

NOTE: Switches S1-SW3 and S1-SW4 are for

future use. Switch S1-SW5 is used to
select supervision.

Setting Supervision

Use switch S1-SW5 on the ANN-1 to select or
deselect supervision. If your ANN-1 has a switch
with position 1 indicated on the left-hand side,
ignore the printing on the switch. SW1 on S1 is at
the extreme right-hand side of S1, regardless of
any other marking.

To set for supervision

S1-SW5 = Closed (ON)

To set for non-supervision

S1-SW5 = Open (OFF)

NOTE: When you select non-supervision for an

annunciator, there must also be one and
only one
 supervised annunciator at the
same address. The supervisory mode is
independent of the network address.

TABLE 3

SWITCH SETTINGS ON THE ANN-1

SWITCH

ADDRESS SETTINGS FOR:

248

249

250

251

S1-SW1

Open-

OFF

Closed-

ON

Open-

OFF

Closed-

On

S1-SW2

Open-

OFF

Open-

OFF

Closed-

ON

Closed-

ON

S1-SW3

Closed-

ON

Closed-

ON

Closed-

ON

Closed-

ON

S1-SW4

Closed-

ON

Closed-

ON

Closed-

ON

Closed-

ON

S1-SW5

See Setting Supervision

Содержание MXL Series

Страница 1: ... Road Florham Park New Jersey 07932 Siemens Building Technologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN TABLE 1 MXL MXLV RACK MOUNT KITS RACK MOUNT KIT MOUNTS MODULE S PLACEMENT ON RACK PANEL HEIGHT X WIDTH TYPE OF SYSTEM ACM RK ACM 1 MMM 1 PIM 1 TBM 1 and TMM 1 Front 17 1 2 X 19 MXLV MKB RK MKB 3 PIM 1 Front 12 1 4 X 19 MXL MXLV MMB RK MMB 1 or PSR 1 Rear 12 1 4 X 19 MXL MXLV MOM RK...

Страница 2: ...tion instructions provided with the module See Table 2 for a list of installation instructions Refer to Figure 2 when assembling the ACM RK to determine correct module placement and cabling connections MKB 3 Installation Remove all system power before installation first battery and then AC To power up connect the AC first and then the battery Setting the Network Address See Figure 3 1 Before insta...

Страница 3: ...Use switch S1 SW5 on the ANN 1 to select or deselect supervision If your ANN 1 has a switch with position 1 indicated on the left hand side ignore the printing on the switch SW1 on S1 is at the extreme right hand side of S1 regardless of any other marking To set for supervision S1 SW5 Closed ON To set for non supervision S1 SW5 Open OFF NOTE When you select non supervision for an annunciator there...

Страница 4: ...ons for mounting the TSP 40 in an MBR 1 backbox 2 After installing the printer to the plate mount the plate to the rack using hardware supplied with the rack Refer to the SYSTEM ASSEMBLY section below and Figures 6 with Voice and 7 without Voice for the recommended location on the rack 3 Mount the dress plate onto the rack with the clear lens centered over the printer paper Fasten in place using h...

Страница 5: ...back of the rack 3 The ACM RK must be mounted below the MKB RK 4 The MOM RK must be mounted below the MMB RK 5 The MPS RK must be mounted below the MOM RK 6 The MMB RK must be mounted directly behind the ACM RK 7 The TSP RK must be located within 24 inches of the MMB RK 8 The VSM RK must be mounted directly below the ACM RK Using the CABLES RK Kit The CABLES RK kit P N 500 893044 has five cables f...

Страница 6: ...ase be sure to follow standard wiring practices 4 E L B A T T I K K R S E L B A C 4 4 0 3 9 8 0 0 5 N P E L B A C E P Y T F O E P Y T M E T S Y S S E C A L P E R S D N E T X E R O S T C E N N O C S E L U D O M E L B A C H T G N E L n o b b i R r o t c u d n o C 4 1 V L X M s e c a l p e R 1 P 1 M C A o t 3 P 1 M M T 4 2 n o b b i R r o t c u d n o C 5 1 V L X M s e c a l p e R 4 P 1 M C A o t P 1 ...

Страница 7: ... Manual P N 315 092036 TABLE 6 Module Termination ALD 2 ALD 2I CMI 300 CSM 4 CZM 4 MMB 1 2 NET 4 7 NIM 1R PIM 1 PSR 1 OCC 1 REP 1 TBM 2 XLD 1 ZAC 30 ZCT 8B MOM 4 MOM 4 MOM 4 MOM 4 MOM 4 TB1 1 4 TB2 1 4 TB3 1 4 TB4 1 9 TB5 1 12 MOM 4 TB1 TB1 1 6 TB4 1 4 TB3 1 4 OMM 1 MOM 4 TB4 All positions TB5 All positions MOM 4 OMM 1 OMM 1 TABLE 5 Module Termination ASC 1 2 Power from EL 410D Batteries CRM 4 CSM...

Страница 8: ...8 Figure 6 MXLV with Voice Mounted on 19 Rack 12 1 4 17 1 2 7 7 12 1 4 9 17 1 2 12 70 8 3 8 ...

Страница 9: ...9 Figure 7 MXL without Voice Mounted on 19 Rack 12 17 1 2 9 12 1 4 12 1 4 70 ...

Страница 10: ...10 Figure 8 Installing the Wiring Duct ...

Страница 11: ...11 ...

Страница 12: ...P N 315 093402 9 Siemens Building Technologies Inc 8 Fernwood Road Florham Park New Jersey 07932 Siemens Building Technologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN ...

Отзывы: