Error Messages and Trouble-Shooting
9-7
FC 56
J31069-D0155-U001-A0-7618
Table 9-2
Error messages via the “error_code” variable
Error Code
(B#16#..)
Description
D0 14
WRITE command:
There is no longer enough memory available in the MDS. Not all the data has been
written to the MDS.
CREATE command:
No data blocks can be reserved when creating a file. No more blocks are free.
D0 15
The MDS could not be identified by the filehandler. Reformat the MDS.
D0 18
The logical address requested lies outside the file. There is an error in the FAT.
Reformat the MDS.
D0 22
The MDS is protected by the COVER command. A write command (e.g. UPDATE,
CREATE) must not modify the memory structure and is therefore rejected.
D0 23
COVER command:
The MDS name specified in the command does not correspond to the actual MDS
name.
D0 24
The wrong UID is entered in the command or the MDS whose UID is entered in the
command is not (or no longer) in the field.
S
Application error. Check UID in the command.
E0 01
S
The type of MDS present at the SLG does not correspond to the ECC operating
mode selected. The MDS must be reformatted to correspond to the desired ECC
operating mode.
S
The MDS is not a filehandler MDS. Format the MDS.
E0 02
No more directory entries available. The file specified in the CREATE command cannot
be created (see section 1.2.2).
E0 03
The file specified with the CREATE command already exists in the directory (no dupli-
cate names).
E0 05
S
A FAT block sequence error has been detected during a READ or WRITE
command. The file allocation table (FAT) is incorrect. The MDS must be reformatted.
S
Invalid address in TRACE command
F0 01
S
The file specified in a command (e.g. WRITE) does not exist in the directory. The
filemust be created with CREATE.
S
Check file name (perhaps not in ASCII format)
S
The QUEUE READ command is to read one or more files which do not exist on the
MDS. Valid data are not transferred to the user.
F0 05
Write attempt (WRITE, UPDATE or DELETE) to a file that may not be changed (pro-
tected by an appropriate attribute).
F0 07
QUEUE READ: The file length specified is shorter than the file length.
F0 08
QUEUE READ: The
“
skip” calculated by the filehandler is greater than 0FFF hex
(4095 in decimal notation).
H1 01
The FC 56 call parameters Params_DB/Params_ADDR are wrong or the Params_DB
parameter doesn’t exist on the PLC.
Содержание MOBY FC 56
Страница 12: ...Introduction 1 6 FC 56 J31069 D0155 U001 A0 7618 ...
Страница 63: ...5 1 FC 56 J31069 D0155 U001 A0 7618 Sample Applications 5 ...
Страница 80: ...Sample Applications 5 18 FC 56 J31069 D0155 U001 A0 7618 ...
Страница 90: ...Entry Exit Check of an MDS in an SLG Field 6 10 FC 56 J31069 D0155 U001 A0 7618 ...
Страница 94: ...System Configuration 7 4 FC 56 J31069 D0155 U001 A0 7618 ...
Страница 100: ...Commissioning Guidelines 8 6 FC 56 J31069 D0155 U001 A0 7618 ...
Страница 101: ...9 1 FC 56 J31069 D0155 U001 A0 7618 Error Messages and Trouble Shooting 9 ...
Страница 152: ...Programming MOBY ASM on PROFIBUS DP V1 B 30 FC 56 J31069 D0155 U001 A0 7618 ...