Commissioning Guidelines
8-3
FC 56
J31069-D0155-U001-A0-7618
4th step: Edit STEP 7 project
The description of this step is based on the included sample program.
S
Copy the sample program for the FC 56 to the STEP 7 project which you just
set up.
S
Continue as shown below based on the number of MOBY channels (number of
SLGs).
– Declare UDT 10 in DB 56 and related MOBY command/s (UDT 50) in DB 57.
– Display DB 56 in the “data view” of the editor, and adjust the “input
parameters” in the “Aktualwert” column. For simple commissioning of MOBY,
all you have to do is adjust the parameters ASM_address and ASM_channel
to the HW Config addresses. General requirement: All MOBY channels
(SLGs) use the same command (DB 57) and the same data (DB 58).
These two variables
must be adjusted for
each channel.
The pointer to command_DB can retain the
default value for initial commissioning.
The value “1” is correct for MOBY I.
Otherwise this value must be adju-
sted.
Figure 8-4 Editing DB 56
S
Edit OB 1, and program a cyclic FC 56 call for each channel. Declare a flag for
the command start for each MOBY channel.
S
Set the variable init_run in the parameter DB in OB 100 for each MOBY
channel.
Содержание MOBY FC 56
Страница 12: ...Introduction 1 6 FC 56 J31069 D0155 U001 A0 7618 ...
Страница 63: ...5 1 FC 56 J31069 D0155 U001 A0 7618 Sample Applications 5 ...
Страница 80: ...Sample Applications 5 18 FC 56 J31069 D0155 U001 A0 7618 ...
Страница 90: ...Entry Exit Check of an MDS in an SLG Field 6 10 FC 56 J31069 D0155 U001 A0 7618 ...
Страница 94: ...System Configuration 7 4 FC 56 J31069 D0155 U001 A0 7618 ...
Страница 100: ...Commissioning Guidelines 8 6 FC 56 J31069 D0155 U001 A0 7618 ...
Страница 101: ...9 1 FC 56 J31069 D0155 U001 A0 7618 Error Messages and Trouble Shooting 9 ...
Страница 152: ...Programming MOBY ASM on PROFIBUS DP V1 B 30 FC 56 J31069 D0155 U001 A0 7618 ...