MJ-XL Operating Procedures
Siemens Power Transmission & Distribution, Inc.
75
L MJ-X
L
Operating Procedures
Use the following instructions as a quick reference for per-
forming many of the standard MJ-XL operating proce-
dures.
View Instantaneous Load Voltage (Vld)
1.
Press Menu key twice
2.
Press Down Arrow once
3.
Read voltage (Vld) on display
View/Reset Max/Min Values
1.
View Meter value or tap position
2.
Press Max/Min key once
3.
Read maximum value on display
4.
To reset maximum value on display, press Cancel
Reset key once
5.
Press Max/Min key again
6.
Read minimum value on display
7.
To reset minimum value on display, press Cancel
Reset key once
View/Set Forward Voltage Level Value
1.
Press Voltage Level Fast-Path key
2.
Read Voltage Level on display
3.
Press Change key - right hand digit will flash
4.
Press Left Arrow key to move left on display or Right
Arrow key to move right on display
5.
Press Up/Down Arrow key to increase or decrease
desired voltage on display - flashing digit will change
6.
Press Save key to save the new Voltage Level
View/Set Bandwidth Value
1.
Press Bandwidth Fast-Path key
2.
Read Bandwidth on display
3.
Press Change key - right hand digit will flash
4.
Press Left Arrow key to move left on display or Right
Arrow key to move right on display
5.
Press Up/Down Arrow key to increase or decrease
desired bandwidth on display - flashing digit will
change
6.
Press Save key to save the new Bandwidth setting
View/Set Time Delay Value
1.
Press Time Delay Fast-Path key
2.
Read time delay on display
3.
Press Change key - right hand digit will flash
4.
Press Left Arrow key to move left on display or Right
Arrow key to move right on display
5.
Press Up/Down Arrow key to increase or decrease
time delay on display - flashing digit will change
6.
Press Save key to save the new time delay value
View/Set Line Drop Compensation Values
1.
Press Resistance Fast-Path key
2.
Read resistive compensation voltage (R) on display
3.
Press Change key - right hand digit will flash
4.
Press Left Arrow key to move left on display or Right
Arrow key to move right on display
5.
Press Up/Down Arrow key to increase or decrease
compensation voltage on display - flashing digit will
change
6.
Press Save key to save the new resistive compensa-
tion voltage value
7.
Press Reactance Fast-Path key
8.
Read reactive compensation voltage (X) on display
9.
Repeat steps 3 to 6 above to set the reactive com-
pensation voltage
View Operation Counter Values
1.
Press Operation Counter Select Fast-Path key (Op
Count)
2.
Read Total Ops count on display
3.
Press Op Count key repeatedly to step through
remaining counter values
View Alerts
1.
Press Alert Status Fast-Path key
2.
Read and note active alert on display
3.
Press Alert Status key repeatedly to step through
remaining active alerts
4.
While viewing alert, press Cancel Reset key to
acknowledge alert
5.
Note: Acknowledging alert does not clear the fault
that caused the alert