4
Setting Up the MJ-XL Control Panel
Siemens Power Transmission & Distribution, Inc.
23
4.4
Setting Control Levels—
the <REGULATOR> Menu
The <
REGULATOR
> Menu defines setpoints used by the
MJ-X
L
Control Panel when operating in Automatic Mode.
Variables in the <
REGULATOR
> Menu are summarized in
Table 4.2 and described in detail in the following sections.
*VRC Stat is a view-only item. It appears in the <
REGULATOR
> menu for viewing convenience.
Table 4.2
The <
REGULATOR
> Menu
DATA ITEM
DESCRIPTION
VALID INPUTS
DEFAULT
INCREMENTS
Forward power flow
Fwd Volts
Voltage setpoint level
106.0 to 134.0
120.0
0.1 Volt
Fwd BW
Bandwidth setpoint
1.0 to 6.0
2.0
0.5 Volt
Fwd Delay
Time delay setpoint
10 to 180
45
1 Second
Fwd Comp(R)
Voltage compensation (Resistive)
- 24 to + 24
0
1 volt
Fwd Comp(X)
Voltage compensation (Reactive)
- 24 to + 24
0
1 Volt
Reverse power flow
Rev Volts
Voltage setpoint level
106.0 to 134.0
120
0.1 Volt
Rev BW
Bandwidth setpoint
1.0 to 6.0
2.0
0.5 Volt
Rev Delay
Time delay setpoint
10 to 180
45
1 Second
Rev Comp(R)
Voltage compensation (Resistive)
- 24 to + 24.
0
1 volt
Rev Comp(X)
Voltage compensation (Reactive)
- 24 to + 24
0
1 Volt
Voltage Reduction Control
VRC Stat*
Present VRC % reduction
0.0 to 10.0
- - -
- - -
VRC Mode:
Voltage Reduction Control mode
OFF, LOCAL, REMOTE,
AUTO
OFF
- - -
VRC Input Special Applications
Alt Delay
Alternate time delay for voltage reduction 1 to 180
5
1 Second
VRC1 In
VRC1 contact configuration
VRC, X-COMP
VRC
- - -
VRC2 In
VRC2 contact configuration
VRC, ALTDELAY, LO XBATT
VRC
- - -
VRC: Local Mode
LOCAL VRC%
Local mode VRC percent reduction
0.0 to 10.0
0
0.1%
VRC: MJ-X
L
remote mode
VRC Stage 1
First stage % reduction
0.0 to 10.0
0
0.1%
VRC Stage 2
Second stage % reduction
0.0 to 10.0
0
0.1%
VRC Stage 3
Third stage % reduction
0.0 to 10.0
0
0.1%
VRC: Remote Mode
VRC Remote
MJ-X
L
or MJ-3A emulation mode
MJ-X
L
or MJ-3A
MJ-XL
- - -
VRC: MJ-3A remote mode
MJ-3A VRC%
MJ-3A % reduction
0.0 to 10.0
0
0.1%
VRC: Automatic mode
AutoVRC set1
VRC setting #1 for Auto VRC
0.0 to 10.0
0
0.1%
AutoVRC set2
VRC setting #2 for Auto VRC
0.0 to 10.0
0
0.1%
AutoVRC1 %I
% Load current #1 for Auto VRC
20 to 150
150
1%
AutoVRC2 %I
% Load current #2 for Auto VRC
20 to 150
150
1%
Voltage Limit Control
VLC Enable
Voltage Limit Control
OFF, ON
OFF
- - -
VLC Upper
Upper limit
106.0 to 134.0
134.0
0.1 V
VLC Lower
Lower limit
106.0 to 134.0
134.0
0.1 V