Reading and Interpreting MJ-XL Control Panel Data
Siemens Power Transmission & Distribution, Inc.
39
5.9
Harmonics Data—
the <HARMONICS> Menu
Harmonics data are calculated for load voltage, source
voltage, and load current. The <
HARMONICS
> Menu
contains the data items listed in Table 5.9:
Use the Menu and Scroll keys to view the <
HARMON-
ICS
> Menu. Use the
Ù
and
Ú
keys to step through the
data items.
The first set of data items in the <
HARMONICS
> Menu
are the three Total Harmonics Distortion values for: load
voltage (Vld THD: NNN.N%), source voltage (Vs THD:
NNN.N%), and load current (Ild THD: NNN.N%). The sec-
ond set of data items in the <
HARMONICS
> Menu are
Show Harm: and Show As:. These data items allow you to
select the format of the data to be viewed:
Show Harm: Odd
Show odd harmonics only
Ev/Odd
Show both even and odd har-
monics.
Show As:
%TOTAL.
Show harmonics as percent-
age of total signal magnitude.
%FUND.
Show harmonics as percent-
age of the fundamental.
RMS Val.
Show harmonics as signal
magnitude.
Use the
Ù
and
Ú
keys in the <
HARMONICS
> Menu to
view the harmonics data. The harmonics data items
appear after configuration items Show Harm and Show
As. The harmonics data items always include the rms and
% Total values for the fundamental (i.e., the 1st harmonic).
Data for even harmonics is only shown if configuration
item Show Harm is set for EV/OD. Data for harmonics
above the 1st harmonic are shown as % Total, % Funda-
mental, or rms depending on which is selected in the
Show As configuration item.
5.10 Local Data Port—
the <COMMUNICATIONS> Menu
The <
COMMUNICATIONS
> Menu contains Local Data
Port status. See Section 4.7 for configuring <
COMMUNI-
CATIONS
> Menu items, such as baud rate, parity,
address, etc.
The <
COMMUNICATIONS
> Menu displays the status
items listed in Table 5.10:
5.11 VRC Status - the <REGULATOR>
Menu
The VRC Status items indicate the present level of Voltage
Reduction Control (VRC). The VRC Status item is indi-
cated as:
VRC Stat = XX.X%MY
where: XX.X% is the amount of voltage reduction
(0.0% to 10.0%)
M is the VRC Mode
where: L = Local
R = Remote
A = Auto (w/Remote Override)
Y is the presently active VRC step
for:
Local - not applicable
Remote - 1, 2, or 3
Auto - 1 or 2
This data item can be accessed using the VRC Select fast-
path key.
Table 5.9
<
HARMONICS
> Menu Data Items
Vld THD = NNN.N%
Vs THD =: NNN.N%
Ild THD =: NNN.N%
Show Harm:
ODD
, EV/OD
Show As: %TOTAL,
%FUND
, RMS VAL.
Vld 1st = NNN.N%T
Vld 1st = NNN.N V
Vld 3rd = NNN.N%F
:
Vld 31st = NNN.N% F
Vs 1st = NNN.N%T
Vs 1st = NNN.N V
Vs 3rd = NNN.N%F.
Vs 31st = NNN.N%F
:
Ild 1st = NNN.N%T
Ild 1st = NNNN A
Ild 3rd = NN.N%F
:
Ild 31st:NN.N%F
Bold
denotes default
Table 5.10
<
COMMUNICATIONS
> Menu Status Items
DATA ITEM
DESCRIPTION
Data Stat =
Communications status conditions
GoodRX
A “good” message (no errors) has
been received
Inact;
Data Port is inactive
LocCtl
MJ-X
L
is in local control (commlink
control is inhibited)
FE RX
Framing Error in received message
OE RX
Overrun Error in received message
NE RX
Noise Error in received message
PE RX
Parity Error in received message
CSE RX
Checksum Error in received message
PTE RQ
Point Type Error (invalid point type
requested)
CME RX
Command Error (invalid command)
received
PNE RX
Point Number Error (Invalid point
number) received