3 Commissioning
International English
MICROMASTER 440 Operating instructions
42
6SE6400-5CA00-0BP0
Note - Busy Message
In some cases - when changing parameter values - the display on the BOP shows
. This means the inverter is busy with tasks of higher priority.
Changing single digits in Parameter values
For changing the parameter value rapidly, the single digits of the display can be
changed by performing the following actions:
Ensure you are in the parameter value changing level (see "Changing parameters
with BOP").
1. Press (function button), which causes the right hand digit to blink.
2. Change the value of this digit by pressing
/
.
3. Press (function button) again causes the next digit to blink.
4. Perform steps 2 to 4 until the required value is displayed.
5. Press
the to leave the parameter value changing level.
Note
The function button may also be used to acknowledge a fault condition
Motor data for parameterization
50 Hz
230/400V
0.61 0.35 A
Cos j0.81
Cos j0.81
65%
0.12kW
2800 / min
3_Mot
IEC 56
IM B3
Nr. ED510 3053
IP54
Rot KL 16
60 Hz
440V Y
0.34A
0.14 kW
3310 /min
S.F. -- 1.15
12.022
I.CI.F
P0308 P0310
P0304
P0309
P0305 P0311
P0307
Figure 3-7
Typical Motor Rating Plate Example