Class 3: Filtered - for residential, commercial and light industry
This level of performance will allow the manufacturer / assembler to self-certify
compliance of their apparatus with the EMC directive for the residential,
commercial and light industrial environment as regards the EMC performance
characteristics of the power drive system. Performance limits are as specified in
the generic emission and immunity standards EN 50081-1 and EN 50082-1.
Table 9-3
Class 3 - Filtered for Residential, Commercial and Light Industry
EMC Phenomenon
Standard
Level
Emissions:
Radiated Emissions*
EN 55011
Level B
Conducted Emissions
EN 55011
Level B
Immunity:
Supply Voltage Distortion
IEC 1000-2-4
(1993)
Voltage Fluctuations, Dips, Unbalance,
Frequency Variations
IEC 1000-2-1
Magnetic Fields
EN 61000-4-8
50 Hz, 30 A/m
Electrostatic Discharge
EN 61000-4-2
8 kV air discharge
Burst Interference
EN 61000-4-4
2 kV power cables, 2 kV control
Radio Frequency Electromagnetic
Field, amplitude modulated
ENV 50 140
80-1000 MHz, 10 V/m, 80% AM, power
and signal lines
Radio-frequency Electromagnetic Field,
pulse modulated
ENV 50 204
900 MHz, 10 V/m 50% duty cycle, 200 Hz
repetition rate
* These limits are dependent on the inverter being correctly installed inside a
metallic switchgear enclosure. The limits will not be met if the inverter is not
enclosed.
Notes
To achieve these performance levels, you must not exceed the default Pulse
frequency nor use cables longer than 25 m.
The MICROMASTER inverters are intended
exclusively for professional
applications
. Therefore, they do not fall within the scope of the harmonics
emissions specification EN 61000-3-2.
Maximum mains supply voltage when filters are fitted is 460 V.
http://nicontrols.com