LOGO!Power
Operating Instructions, 06.2014, C98130-A7560-A999-3-7629
47
Applications
9
9.1
Parallel connection to increase power rating
To enhance performance, two LOGO!Power power supplies of the same type can be
galvanically connected in parallel.
The following must be observed:
●
The cables connected to each power supply at terminals "+" and "-" must have identical
lengths and the same cable cross-sections (or the same impedance) up to a common
external network junction (terminal strip) if possible.
●
The parallel-switched power supplies must be switched on simultaneously with a common
switch in the mains supply line (e.g. with the main switch available in control cabinets).
●
The output voltages measured in no-load operation for the power supplies that are not yet
connected in parallel should not deviate more than a maximum of 0.2%. This usually
corresponds to the factory setting. If the output voltage is changed, you should connect
the "-" terminals and then, in no-load operation, measure the voltage difference between
the "+" terminals that have not yet been connected. The voltage difference should not
exceed 0.2%.
Figure 9-1
Parallel connection, correct and incorrect
Содержание LOGO!Power 6EP1332-1SH52
Страница 8: ...Safety instructions LOGO Power 8 Operating Instructions 06 2014 C98130 A7560 A999 3 7629 ...
Страница 26: ...Installation 5 2 Output side connection LOGO Power 26 Operating Instructions 06 2014 C98130 A7560 A999 3 7629 ...
Страница 40: ...Technical data 6 9 Dimension drawing LOGO Power 40 Operating Instructions 06 2014 C98130 A7560 A999 3 7629 ...
Страница 54: ...Environment LOGO Power 54 Operating Instructions 06 2014 C98130 A7560 A999 3 7629 ...