LOGO!Power
Operating Instructions, 06.2014, C98130-A7560-A999-3-7629
27
Technical data
6
Note
For an AC input voltage, the technical data is applicable for rated input voltage, rated load
and +25° C ambient temperature (if nothing else is specified).
6.1
Input
6EP1311-1SH03
(5 V / 3 A)
6EP1311-1SH13
(5 V / 6.3 A)
6EP1321-1SH03
(12 V / 1.9 A)
6EP1322-1SH03
(12 V / 4.5 A)
6EP1351-1SH03
(15 V / 1.9 A)
Input
1-phase AC or DC
Rated voltage
U
e rated / for AC
100...240 V
Voltage range / for AC 85...264 V
Input voltage / for DC 110…300 V
Wide-range input
Yes
Overvoltage
resistance
2.3 x Ue rated, 1.3 ms
Mains buffering at
Ia rated, min.
40 ms
40 ms
40 ms
40 ms
40 ms
Mains buffering
at Ue = 187 V
Rated line frequency
50/60 Hz
Line frequency range 47...63 Hz
Input current / at rated
value of input voltage
120 V
0.36 A
0.71 A
0.53 A
1.13 A
0.63 A
Input current / at rated
value of input voltage
230 V
0.22 A
0.37 A
0.3 A
0.61 A
0.33 A
Switch-on current
limitation (+ 25° C),
max.
26 A
50 A
25 A
55 A
25 A
I²t, max.
0.8 A²·s
3 A²·s
0.8 A²·s
3 A²·s
0.8 A²·s
Built-in line-side fuse
Internal
Protection in the line
feeder cable (IEC 898)
Recommended miniature circuit-breaker: Characteristic B from 16 A or characteristic C from 10 A
Содержание LOGO!Power 6EP1332-1SH52
Страница 8: ...Safety instructions LOGO Power 8 Operating Instructions 06 2014 C98130 A7560 A999 3 7629 ...
Страница 26: ...Installation 5 2 Output side connection LOGO Power 26 Operating Instructions 06 2014 C98130 A7560 A999 3 7629 ...
Страница 40: ...Technical data 6 9 Dimension drawing LOGO Power 40 Operating Instructions 06 2014 C98130 A7560 A999 3 7629 ...
Страница 54: ...Environment LOGO Power 54 Operating Instructions 06 2014 C98130 A7560 A999 3 7629 ...