Technical data
6.1 Input
LOGO!Power
28
Operating Instructions, 06.2014, C98130-A7560-A999-3-7629
6EP1352-1SH03
(15 V / 4 A)
6EP1331-1SH03
(24 V / 1.3 A)
6EP1332-1SH43
(24 V / 2.5 A)
6EP1332-1SH52
(24 V / 4 A)
Input
1-phase AC or DC
Rated voltage
U
e rated / for AC
100...240 V
Voltage range / for AC 85...264 V
Input voltage / for DC 110…300 V
Wide-range input
Yes
Overvoltage resistance 2.3 x Ue rated, 1.3 ms
Mains buffering at
Ia rated, min.
40 ms
40 ms
40 ms
40 ms
Mains buffering
at Ue = 187 V
Rated line frequency
50/60 Hz
Line frequency range 47...63 Hz
Input current / at rated
value of input voltage
120 V
1.24 A
0.7 A
1.22 A
1.95 A
Input current / at rated
value of input voltage
230 V
0.68 A
0.35 A
0.66 A
0.97 A
Switch-on current
limitation (+ 25° C),
max.
55 A
25 A
46 A
30 A
I²t, max.
3 A²·s
0.8 A²·s
3 A²·s
2.5 A²·s
Built-in line-side fuse
Internal
Protection in the line
feeder cable (IEC 898)
Recommended miniature circuit-breaker: Characteristic B from 16 A or characteristic C from 10 A
Figure 6-1
Mains buffering
Содержание LOGO!Power 6EP1332-1SH52
Страница 8: ...Safety instructions LOGO Power 8 Operating Instructions 06 2014 C98130 A7560 A999 3 7629 ...
Страница 26: ...Installation 5 2 Output side connection LOGO Power 26 Operating Instructions 06 2014 C98130 A7560 A999 3 7629 ...
Страница 40: ...Technical data 6 9 Dimension drawing LOGO Power 40 Operating Instructions 06 2014 C98130 A7560 A999 3 7629 ...
Страница 54: ...Environment LOGO Power 54 Operating Instructions 06 2014 C98130 A7560 A999 3 7629 ...