Installation
5
WARNING
Hazard due to electric shock
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again. If this instruction is
not observed, touching live parts can result in death or serious injury.
5.1
Line-side connection
The LOGO!Power power supplies are power packs according. to safety class II (without
protective conductor or equivalent without PE). LOGO!Power are designed for connection to
a 1-phase AC supply network (TN or TT system according to VDE 0100 T 300 / IEC 364-3)
with rated voltage 1-phase 100-240 VAC, 50/60 Hz or to a power supply with 110-300 VDC.
Figure 5-1
Line connection
The line supply is connected using terminal L1 and N (see Figure 5-1 Line connection
(Page 23)), and must be implemented according to IEC 60364 and EN 50178. A protective
device (miniature circuit-breaker or circuit-breaker) and a disconnection unit for the power
supply must be provided. A ground-fault circuit interrupter must not be used as the only
protective measure against indirect contact; this applies to the entire supply system that is
protected by the residual current operated circuit-breaker.
Содержание LOGO!Power 6EP1332-1SH52
Страница 8: ...Safety instructions LOGO Power 8 Operating Instructions 06 2014 C98130 A7560 A999 3 7629 ...
Страница 26: ...Installation 5 2 Output side connection LOGO Power 26 Operating Instructions 06 2014 C98130 A7560 A999 3 7629 ...
Страница 40: ...Technical data 6 9 Dimension drawing LOGO Power 40 Operating Instructions 06 2014 C98130 A7560 A999 3 7629 ...
Страница 54: ...Environment LOGO Power 54 Operating Instructions 06 2014 C98130 A7560 A999 3 7629 ...