A5E00067781 01
Description of function
When the state at the input Trg changes to 1, the output Q
switches to 1 immediately.
If the state at the input Trg changes from 1 to 0, the current
time T
a
starts in LOGO!, and the output remains set. If T
a
reaches the values specified via T (T
a
=T), the output Q is
reset to 0 (off delay).
If the Trg input switches on and off again, the time T
a
starts
again.
The input R (Reset) resets the elapsed time T
a
and the out-
put before the set time delay T
a
has elapsed.
In the event of a power failure, the elapsed time is reset.
LOGO! Functions