197
LOGO! Manual
A5E00067781 01
LOGO! 24RCL
LOGO! 24RCLB11
LOGO! 24L
Digital outputs
Number
8
8
Output type
Transistor, current–
sourcing
Relay outputs
Electrical isolation
No
Yes
In groups of
2
Activation of digital input
Yes
Yes
Output voltage
Supply voltage
Output current
Max. 0.3 A
Continuous current I
th
(per
connector)
Max. 10 A
Incandescent lamp load
(25,000 switching cycles) at
1000 W
Fluorescent tubes with electr.
control gear (25,000 switch-
ing cycles)
10 x 58 W
Fluorescent tubes, conven-
tionally compensated (25,000
switching cycles)
1 x 58 W
Fluorescent tubes, uncom-
pensated (25,000 switching
cycles)
10 x 58 W
Short circuit–proof and over-
load–proof
Yes
Short–circuit current limitation
Approx. 1 A
Derating
None throughout
the entire tempera-
ture range
None throughout
the entire tempera-
ture range
Short circuit–proof cos 1
Power protection
B16
600A