LOGO! Manual
A5E00067781 01
Example
To control a heating system, the flow temperature T
v
(via a
sensor at AI1) and the return temperature T
r
(via a sensor
at AI2) are to be compared with each other.
If the return temperature differs by more than 15
C from
the flow temperature, a switching operation is to be trig-
gered (e.g. burner on).
The real temperatures are to be displayed in PARAM
mode.
Temperature sensors with the following technical specifica-
tions are available: –30 to +70
C, 0 to 10V DC.
Application
Internal Representation
–30 to +70
C = 0 to 10V DC
0 to 1000
0
C
300
Offset = –300
Value range:
–30 to +70
C = 100
1000
Gain = 100/1000
= 0.1 = 10 %
Switching threshold = 15
C
Threshold value = 15
Parameter assignment
B03:Par
=00015
=0010+
=-300
Display in PARAM mode (examples):
B03:Par
= 20
Ax
= 10
Ay
= 30
B03:Par
=
30
Ax
=
10
Ay
=– 20
LOGO! Functions