General functions
6.1
Reading the current temperatures and valve modes
1. Press
Info
to access
Main overview
.
2. Here you can see information about the
connected heating circuit and hot water circuit.
3. Scroll down in the menu with the navigation
dial.
6.2
Frost protection
Regardless of the selected operating mode and settings for pump start and indoor temperature, the heat will be
activated if the outside temperature drops below approxi1.5°C (factory set).
This function is installed to protect buildings and heating systems from frost. The hot water circuit also has a
frost protection function that cannot be turned off.
For each heating circuit and hot water circuit it is possible to set a range of temperatures to enable the frost
protection.
If the pumps are turned off in manual pump mode, this function does not apply.
The frost protection for the plant works in two ways.
•
If the outside temperature is lower than the set temperature Setp.plant frost about +1.5°C the pumps
are activated every six hours for at least 10 minutes.
•
If the outside temperature drops by 5° below the set temperature Setp.plant frost the pumps will run
continuously.