IQHeat
User manual
14
5.4
Alarms and their classification
All sensors use function alarms that are enabled when, for example, there is a cable break or short circuit. On
top of this, there are several different types of level alarms; high-level and low-level where the size of the
sensors' level can be limited. These level alarms are filtered with a delay time.
A selection of alarms is displayed in the table below.
Designation
Name
Class
Remark
Pump heating circuit
A
Signal input from pump
Frost alarm
Level alarm
A
See description in point 2
Heating circuit, Supply
Function alarm sensor
A
Hot water supply
Function alarm sensor
A
Primary, Supply
Function alarm sensor
B
Outside temperature
Function alarm sensor
A
Outside temperature is set to -1° C
Heating circuit, Return
Function alarm sensor
B
High level, high and low pressure
Heating circuit pressure/level Level alarm, pressure
B
High level or high and low pressure
Temp deviation, Heat
Control deviation,
heating circuit
B
Adjustable level and delay
Temp deviation Hot Water
Control deviation, hot
water
B
Adjustable level and delay
HWC-temperature
Function alarm sensor,
level alarm
B/B
Low level
Secondary circuit, Supply
Function alarm sensor
A
Secondary circuit, Return
Function alarm sensor,
level alarm
B/B
Temp deviation Cooling
Control deviation
cooling circuit
B
Adjustable level and delay