Description
3-22
6ZB5 430–0BH02–1AA0
Siemens AG 1996 All Rights Reserved
SINUMERIK 805SM / 840C (BS)
3.3
Description of the L2-DP slave up to V3.x
Note
This section only applies if
The IM 328–N module with the order number 6FC5 012–0CA01–0AA0
is used
or
The module with the order number 6FC5 012–0CA03–0AA0 is used and
jumper X999 is set for operation as a SINEC L2–DP slave up to V3.x
(see Section 2.1.1).
3.3.1
Notes on parameterization of the slave
Here are some notes on how to use the IM 328–N as an L2–DP slave up to
V3.x in the ET 200 Distributed I/O System.
For example, the master IM 308–B or IM 329–N can be used.
If the IM 308–B or IM 329–N module is the master, then
PG/PC with COM ET 200 (V4.x)
Note
About the system parameter BUS PROFILE:
Select one of the bus profiles
“DP up to V.3x”
No DP standard slaves and no FMS stations
(e.g. IM 328)
“DP standard”
DP Siemens slaves, standard slaves but not
FMS stations or
“DP/FMS”
DP Siemens slaves, standard slaves and FMS slaves.
With this setting, the bus profile is set for the entire bus (timeout settings
etc.).
About the baud rate:
Baud rates up to 1500 kBaud are possible.
Preconditions
for slave para-
meterization
ET 200
system parameters
3.3 Description of the L2-DP slave up to V3.x