Wiring Diagram
1
Signal input "setpoint shift"
2
Measuring neutral
4
0 to 10 Vdc output/cooling
5
Ground for 0 to 10 Vdc
output/cooling
6
Operating voltage 24 Vac negative
7
Operating voltage 24 Vac positive
8
Positive control for 3-pos actuator
9
Return control signal open
10
Return control signal close
D1
Signal input for potential-free
operating mode changeover switch
GND
Ground
Figure 12. Wiring Diagram.
NOTE:
When wiring to an SSC81.5U actuator, an earth ground, isolating, Class 2
transformer is recommended. However, if you use an auto or polarized
transformer, the wiring polarity must be maintained through the controller to
the SSC81.5U for proper operation. For example, if G/G0 are reversed to the
controller, they must also be reversed to the actuator.