background image

 

Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as 
design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. © 2016 
Siemens Industry, Inc.

 

Siemens Industry, Inc. 

Building Technologies Division 
1000 Deerfield Parkway 
Buffalo Grove, IL 60089 
Tel. + 1 847-215-1000 

Your feedback is important to us. If you have 
comments about this document, please send them 
t

[email protected]

 

 

Document No. 155-328P25 

Printed in the USA 

Page 11 

 

 

Wiring Diagram 

 

Signal input "setpoint shift" 

Measuring neutral 

0 to 10 Vdc output/cooling 

Ground for 0 to 10 Vdc 

 

output/cooling 

Operating voltage 24 Vac negative 

Operating voltage 24 Vac positive 

Positive control for 3-pos actuator 

Return control signal open 

10 

Return control signal close 

D1 

Signal input for potential-free 

 

operating mode changeover switch 

GND 

Ground 

 

 

 

Figure 12.  Wiring Diagram. 

 

NOTE: 

When wiring to an SSC81.5U actuator, an earth ground, isolating, Class 2 
transformer is recommended. However, if you use an auto or polarized 
transformer, the wiring polarity must be maintained through the controller to 
the SSC81.5U for proper operation. For example, if G/G0 are reversed to the 
controller, they must also be reversed to the actuator. 

Dimensions 

All dimensions in 
inches 
(millimeters) 

 

 

 

Figure 13.  RCU61U Dimensions. 

Figure 14.  Base Plate Dimensions. 

 

Содержание Free Energy Band RCU61U

Страница 1: ...ing Three position output 24 Vac for heating Operating modes Normal Energy Saving Frost Protection Standby and Off Active 0 to 10 Vdc input for setpoint shifting Operating mode changeover input for remote control Adjustable minimum limitation for cooling output Deadband between heating and cooling Operating voltage 24 Vac Application Individual room temperature control in HVAC installations that a...

Страница 2: ...Acting D A The proportional band or the switching differential can be 2 F or 7 F 1 C or 4 C in heating mode and 1 F or 3 5 F 0 5 C or 2 C in cooling mode selectable with DIP Switch No 4 Heating Cooling with Minimum Limitation Cooling T Room or return air temperature L L10 Output percentage W Room temperature set point Xdz Deadband XpH Proportional band heating XpC Proportional band cooling VR 0 to...

Страница 3: ...The neutral position is at 5 Vdc and means no setpoint shift W Original setpoint W1 New setpoint at 10V input W2 New setpoint at 0V input V Input voltage Figure 3 Setpoint Shifting Setpoint Limit Stops The room temperature setpoint can be limited in increments of 2 F 1 C by using the minimum and maximum setpoint limit stops This prevents arbitrary setpoint readjustments To set limit stops remove t...

Страница 4: ...alls below 46 F 8 C the controller will automatically switch to frost protection mode In that case the heating valve opens and the room temperature is maintained at a setpoint of 46 F 8 C Any adjustments you make to the setpoint will be ignored Operating Mode Changeover Switch A changeover switch can be connected to status input D1 GND When the switch closes its contact caused by an open window fo...

Страница 5: ... mode1 1 F 0 5 C in cooling mode1 7 F 4 C in heating mode 3 5 F 2 C in cooling mode 5 Dead zone Xdz 3 5 F 2 C 1 9 F 5 C 6 Cooling signal output in energy saving mode Active Inactive1 1 Factory setting Accessories ARG70 Adapter Plate for 2 4 inch or 4 4 inch conduit boxes QAH11 1 Changeover remote sensor Notes Check the settings of DIP Switches No 1 through No 6 and change them if required After ap...

Страница 6: ...s after controller power up User input using setpoint knob results in instantaneous response There is a one minute delay before changes made to temperature sensing and changeover are implemented Drywall Mounting 1 Insert a small screwdriver into the bottom of the controller and press in the tab located in the center of the controller 2 Lift the bottom of the controller from the controller base and...

Страница 7: ...s Industry Inc Page 7 Drywall Mounting Continued 12 Terminate the wires per wiring instructions located above the terminal block Figure 8 Wiring Termination 13 Reattach the controller to the controller base Figure 9 Controller Reattachment 14 Adjust the setpoint dial to the desired setting The installation is now complete ...

Страница 8: ...r base and push up to remove the cover from the two tabs located at the top of the controller base 3 Separate the controller base 5 from the controller 6 4 Using the four screws provided fasten the wall box adapter 3 to the plaster ring 2 Plaster ring supplied by others 5 Flex the adapter mask 4 and snap it in place inside the wall box adapter 3 6 Pull wires through the plaster ring 2 7 Fasten the...

Страница 9: ... the bottom of the controller from the controller base and push up to remove the cover from the two tabs located at the top of the controller base 3 Separate the controller base 5 from the controller 6 4 Using the two screws provided fasten the wall box adapter 3 to the wall box 1 5 Flex the adapter mask 4 and snap it in place inside the wall box adapter 3 6 Fasten the controller base 5 to the wal...

Страница 10: ...ltage 0 to 10 Vdc Current 1 mA Control output Terminals 9 and 10 Three position output Voltage 24 Vac 20 Current 2A maximum Motor timing for heating output 150 seconds at 50 60 Hz Status input D1 Contact sensing 6 to 15 Vdc 3 to 6 mA Insulation against mains voltage 4 kV Maximum number of contacts connected 50 in parallel Status input terminal 1 Setpoint shift of 22 5 F 12 5 C 0 to 10 Vdc Neutral ...

Страница 11: ...etpoint shift 2 Measuring neutral 4 0 to 10 Vdc output cooling 5 Ground for 0 to 10 Vdc output cooling 6 Operating voltage 24 Vac negative 7 Operating voltage 24 Vac positive 8 Positive control for 3 pos actuator 9 Return control signal open 10 Return control signal close D1 Signal input for potential free operating mode changeover switch GND Ground Figure 12 Wiring Diagram NOTE When wiring to an ...

Отзывы: