background image

Technical Instructions 

RCU61U Room Temperature Controller 

Document Number 155-328P25 

for CAV Systems 

October 6, 2016 

Page 4 

 

Siemens Industry, Inc. 

 

Operating Modes 

The following operating modes are available: 

Normal 

When dry contact (3) is open, the setpoint knob setting takes over control and normal 
mode is initiated. 

Energy Saving 

Energy saving mode can be initiated by activating the external operating mode 
changeover switch, if DIP Switch No. 1 is set to 

ON

In energy saving mode, the heating setpoint is 61°F (16°C) and the cooling setpoint is 
82°F (28°C), independent of the position of the setpoint knob. 

When the DIP switch is in energy saving mode and the fan speed control is set to 
standby, the energy saving mode takes precedence over standby mode. Low fan speed 
will be selected even though the fan switch is on standby. 

Frost Protection 

Frost protection mode can be initiated by activating the external operating mode 
changeover switch, if DIP Switch No. 1 is set to 

OFF

If the room temperature falls below 46°F (8°C), the controller will automatically switch to 
frost protection mode. In that case, the heating valve opens and the room temperature 
is maintained at a setpoint of 46°F (8°C). Any adjustments you make to the setpoint will 
be ignored. 

Operating Mode 
Changeover Switch 

A changeover switch can be connected to status input D1

–GND. When the switch 

closes its contact (caused by an open window, for instance), the operating mode will 
change from normal operation or standby to energy saving mode (if DIP Switch No. 1 is 
set to 

ON

), or from normal operation or energy saving mode to standby (if DIP Switch 

No. 1 is set to 

OFF

).  

The operating action of the switch (Normally Closed - NC or Normally Open - NO) can 
be selected. 

Mechanical Design 

The unit consists of two parts: 

  A plastic housing which accommodates the electronics, the operating elements, and  

the built-in room temperature sensor. 

  A controller base. 

The housing snaps into the top and bottom of the mounting base. 

The screw terminals are mounted on the base. The DIP switches and the potentiometer 
are located at the rear of the unit. To access the DIP switches, remove the controller 
from the controller base. See Figure 5. 

 

Figure 5.  DIP Switch Settings. 

Содержание Free Energy Band RCU61U

Страница 1: ...ing Three position output 24 Vac for heating Operating modes Normal Energy Saving Frost Protection Standby and Off Active 0 to 10 Vdc input for setpoint shifting Operating mode changeover input for remote control Adjustable minimum limitation for cooling output Deadband between heating and cooling Operating voltage 24 Vac Application Individual room temperature control in HVAC installations that a...

Страница 2: ...Acting D A The proportional band or the switching differential can be 2 F or 7 F 1 C or 4 C in heating mode and 1 F or 3 5 F 0 5 C or 2 C in cooling mode selectable with DIP Switch No 4 Heating Cooling with Minimum Limitation Cooling T Room or return air temperature L L10 Output percentage W Room temperature set point Xdz Deadband XpH Proportional band heating XpC Proportional band cooling VR 0 to...

Страница 3: ...The neutral position is at 5 Vdc and means no setpoint shift W Original setpoint W1 New setpoint at 10V input W2 New setpoint at 0V input V Input voltage Figure 3 Setpoint Shifting Setpoint Limit Stops The room temperature setpoint can be limited in increments of 2 F 1 C by using the minimum and maximum setpoint limit stops This prevents arbitrary setpoint readjustments To set limit stops remove t...

Страница 4: ...alls below 46 F 8 C the controller will automatically switch to frost protection mode In that case the heating valve opens and the room temperature is maintained at a setpoint of 46 F 8 C Any adjustments you make to the setpoint will be ignored Operating Mode Changeover Switch A changeover switch can be connected to status input D1 GND When the switch closes its contact caused by an open window fo...

Страница 5: ... mode1 1 F 0 5 C in cooling mode1 7 F 4 C in heating mode 3 5 F 2 C in cooling mode 5 Dead zone Xdz 3 5 F 2 C 1 9 F 5 C 6 Cooling signal output in energy saving mode Active Inactive1 1 Factory setting Accessories ARG70 Adapter Plate for 2 4 inch or 4 4 inch conduit boxes QAH11 1 Changeover remote sensor Notes Check the settings of DIP Switches No 1 through No 6 and change them if required After ap...

Страница 6: ...s after controller power up User input using setpoint knob results in instantaneous response There is a one minute delay before changes made to temperature sensing and changeover are implemented Drywall Mounting 1 Insert a small screwdriver into the bottom of the controller and press in the tab located in the center of the controller 2 Lift the bottom of the controller from the controller base and...

Страница 7: ...s Industry Inc Page 7 Drywall Mounting Continued 12 Terminate the wires per wiring instructions located above the terminal block Figure 8 Wiring Termination 13 Reattach the controller to the controller base Figure 9 Controller Reattachment 14 Adjust the setpoint dial to the desired setting The installation is now complete ...

Страница 8: ...r base and push up to remove the cover from the two tabs located at the top of the controller base 3 Separate the controller base 5 from the controller 6 4 Using the four screws provided fasten the wall box adapter 3 to the plaster ring 2 Plaster ring supplied by others 5 Flex the adapter mask 4 and snap it in place inside the wall box adapter 3 6 Pull wires through the plaster ring 2 7 Fasten the...

Страница 9: ... the bottom of the controller from the controller base and push up to remove the cover from the two tabs located at the top of the controller base 3 Separate the controller base 5 from the controller 6 4 Using the two screws provided fasten the wall box adapter 3 to the wall box 1 5 Flex the adapter mask 4 and snap it in place inside the wall box adapter 3 6 Fasten the controller base 5 to the wal...

Страница 10: ...ltage 0 to 10 Vdc Current 1 mA Control output Terminals 9 and 10 Three position output Voltage 24 Vac 20 Current 2A maximum Motor timing for heating output 150 seconds at 50 60 Hz Status input D1 Contact sensing 6 to 15 Vdc 3 to 6 mA Insulation against mains voltage 4 kV Maximum number of contacts connected 50 in parallel Status input terminal 1 Setpoint shift of 22 5 F 12 5 C 0 to 10 Vdc Neutral ...

Страница 11: ...etpoint shift 2 Measuring neutral 4 0 to 10 Vdc output cooling 5 Ground for 0 to 10 Vdc output cooling 6 Operating voltage 24 Vac negative 7 Operating voltage 24 Vac positive 8 Positive control for 3 pos actuator 9 Return control signal open 10 Return control signal close D1 Signal input for potential free operating mode changeover switch GND Ground Figure 12 Wiring Diagram NOTE When wiring to an ...

Отзывы: