Periphery board (500p) FCI2017
Technical data
2
42 | 46
Building Technologies
A6V10315038_f_en_--
Siemens Industry, Inc.
2016-02-25
2.12 Technical data
Supply input
Plug strip
X301/302
Operating voltage
DC 24 V nominal, filtered
Operating current (standby)
120 mA
Max. operating current.
136 mA
Input current (active)
Design
●
PS170W (only fire detection
systems) 6.5 A at
●
1 x PS300W 11.5 A
●
2 x PS300W 20 A
Not power limited
Battery
Plug strip
X303
Voltage
DC 20.4 V…DC 26.4 V
(DC 24 V nominal)
Curent
11.5 A
NAC circuit
Plug strip
X601
Voltage
DC 24 V
Special Application for strobe loads
Regulated for non-pulsing loads
Standby operating current
Max. 10 mA
Active operating current
Max. 1x class A circuit or 2x class B
circuits
Max. 3 A for 1x class A circuit
Max. 3 A per class B circuit
2x 3 A = 6 A for 2x class B circuits
Maximum circuit resistance
1.4
Ω
@ 3.0 A
Supervised for
●
Open circuit
●
Short circuit
●
Ground fault
Design
●
Short-circuit protection
●
Voltage surge protection
●
Power limited
AUX output
Plug strip
X1001
Voltage
DC 24 V nominal "Special Application"
For use with: FN2006/FN2007, HZM,
HCP, FCA2018, FT2014/FT2015,
FTI2001
Curent
Max. 1.5 A
Design
●
Short-circuit protection
●
Voltage surge protection
●
Power limited