Periphery board (250p) FCI2016
Views
1
9 | 46
Building Technologies
A6V10315038_f_en_--
Siemens Industry, Inc.
2016-02-25
Element
Des.
Function
Fuses
F301
30 A fuse for battery
F302
Fuse 20 A for voice alarm DC 24 V output
Indicators
H1301
Status display for circuit card 1 (circuits 1 and 2)
Adjustment elements
S100
Reset key for periphery processor (without circuits)
Jumpers
X403
Degraded mode ALARM SILENCEABLE/NON SILENCEABLE
X602
Degraded mode ENABLE/DISABLE NAC 1 class A or NAC 1-1 class B
X603
Degraded mode ENABLE/DISABLE NAC 1-2 class B
X604
NAC 1 class A/B selection
X605
NAC 1 class A/B selection
X606
NAC 1 class A/B selection
X305
Power supply 2 ON/OFF
Connector
X201
Peripheral data bus to the PMI & mainboard
X202
Peripheral data bus output
X204
Future extension (not used)
X301
Connector for power supply 1 (PS1)
X302
Connector plug for power supply 2 (PS2) in housing (3HU)
X303
Battery connection
X304
DC 24 V connection to Card Cage VCA2002 for feed to the voice alarm
modules and associated peripherals
X601
NAC1 output
X801
BELL follower input
X901
NAC 2 extension or releasing module
X902
Leased line / city tie module
X1001
Output DC 24 V AUX
X1101
Plug block for relay connections
X1302
For future application
X1401
Detector circuit circuit card 1, circuit 1
X1402
Detector circuit circuit card 1, circuit 2